We appreciate your visit to An air conditioner takes outside air at 35 C and cools it to 15 C at a rate of 1 kg s Estimate the amount. This page offers clear insights and highlights the essential aspects of the topic. Our goal is to provide a helpful and engaging learning experience. Explore the content and find the answers you need!
Answer :
Answer:
Q=20.1kW
recirculation mode=Q=9.045kW
Explanation:
Hi!
To solve this problem you must use the first law of thermodynamics that establishes the energy that enters a system is the same that must come out. Given the above we have the following equation
Q = mCp (T2-T1)
WHERE
Q = Heat removed to air
m = mass air flow = 1kg / s
Cp = specific heat of air = 1.005KJ / kg
°C
T2 = air inlet temperature
T1 = air outlet temperature=15°C.
for the first case
Q=(1kg/s)(1.005KJ/kg°C)(35°C-15°C)
Q=20.1kW
for the second case( recirculation mode)
Q=(1kg/s)(1.005KJ/kg°C)(24°C-15°C)
Q=9.045kW
Thanks for taking the time to read An air conditioner takes outside air at 35 C and cools it to 15 C at a rate of 1 kg s Estimate the amount. We hope the insights shared have been valuable and enhanced your understanding of the topic. Don�t hesitate to browse our website for more informative and engaging content!