College

We appreciate your visit to An air conditioner takes outside air at 35 C and cools it to 15 C at a rate of 1 kg s Estimate the amount. This page offers clear insights and highlights the essential aspects of the topic. Our goal is to provide a helpful and engaging learning experience. Explore the content and find the answers you need!

An air conditioner takes outside air at 35°C and cools it to 15°C at a rate of 1 kg/s. Estimate the amount of power needed to do this.

Recalculate the needed power if it is put in recirculation mode using inside air at 24°C and cools that to 15°C.

Answer :

Answer:

Q=20.1kW

recirculation mode=Q=9.045kW

Explanation:

Hi!

To solve this problem you must use the first law of thermodynamics that establishes the energy that enters a system is the same that must come out. Given the above we have the following equation


Q = mCp (T2-T1)

WHERE

Q = Heat removed to air

m = mass air flow = 1kg / s

Cp = specific heat of air = 1.005KJ / kg
°C

T2 = air inlet temperature

T1 = air outlet temperature=15°C.

for the first case

Q=(1kg/s)(1.005KJ/kg°C)(35°C-15°C)

Q=20.1kW

for the second case( recirculation mode)

Q=(1kg/s)(1.005KJ/kg°C)(24°C-15°C)

Q=9.045kW

Thanks for taking the time to read An air conditioner takes outside air at 35 C and cools it to 15 C at a rate of 1 kg s Estimate the amount. We hope the insights shared have been valuable and enhanced your understanding of the topic. Don�t hesitate to browse our website for more informative and engaging content!