We appreciate your visit to If the fault current is 2 kA the relay setting is 50 and the CT ratio is 400 5 then the plug setting multiplier of. This page offers clear insights and highlights the essential aspects of the topic. Our goal is to provide a helpful and engaging learning experience. Explore the content and find the answers you need!

If the fault current is 2 kA, the relay setting is 50, and the CT ratio is 400/5, then the plug setting multiplier of the relay will be: _________

Answer :

Final answer:

The plug setting multiplier (PSM) of a relay given a fault current of 2kA, relay setting of 50, and a CT ratio of 400/5 is calculated to be 0.04.

Explanation:

The question is related to calculating the plug setting multiplier (PSM) of a relay in an electrical system. To find the PSM, we use the formula:

PSM = Fault Current (secondary side) / (CT ratio * Relay setting)

Given the fault current is 2kA, the relay setting is 50, and the CT (current transformer) ratio is 400/5, we can convert the primary fault current to the secondary side of the CT before applying the formula:

Fault current on the secondary side = Fault Current (primary side) / CT ratio

Fault current on the secondary side = 2000 A (2kA) / (400/5)

Fault current on the secondary side = 2000 A * 5 / 400

Fault current on the secondary side = 10 A

Now, we will calculate the PSM:

PSM = 10 A / (5 A * 50)

PSM = 10 A / 250 A

PSM = 0.04

Therefore, the plug setting multiplier of the relay is 0.04.

Thanks for taking the time to read If the fault current is 2 kA the relay setting is 50 and the CT ratio is 400 5 then the plug setting multiplier of. We hope the insights shared have been valuable and enhanced your understanding of the topic. Don�t hesitate to browse our website for more informative and engaging content!