We appreciate your visit to An 18 000 Btu h split air conditioner is running at full load to keep a room at 25 C in an environment at 45. This page offers clear insights and highlights the essential aspects of the topic. Our goal is to provide a helpful and engaging learning experience. Explore the content and find the answers you need!
Answer :
COP of the air conditioning unit is 7.596, and the rate at which heat is rejected to the ambient from the air conditioner condenser is 21.49 kW.
To determine the Coefficient of Performance (COP) of the 18,000 Btu/h split air conditioner and the rate at which heat is rejected to the ambient from the air conditioner condenser, follow these steps:
1. Convert the air conditioner capacity from Btu/h to kW:
18,000 Btu/h * (1,055 kJ / 1 Btu) * (1 kW / 1,000 kJ) = 18,990 W = 18.99 kW
2. Calculate the COP:
COP = Cooling Capacity (kW) / Power Input (kW)
COP = 18.99 kW / 2.5 kW = 7.596
3. Calculate the heat rejected to the ambient:
Heat Rejected = Cooling Capacity + Power Input
Heat Rejected = 18.99 kW + 2.5 kW = 21.49 kW
So, the COP of the air conditioning unit is 7.596, and the rate at which heat is rejected to the ambient from the air conditioner condenser is 21.49 kW.
Know more about Heat Rejection here:
https://brainly.com/question/29498231
#SPJ11
Thanks for taking the time to read An 18 000 Btu h split air conditioner is running at full load to keep a room at 25 C in an environment at 45. We hope the insights shared have been valuable and enhanced your understanding of the topic. Don�t hesitate to browse our website for more informative and engaging content!
- Why do Businesses Exist Why does Starbucks Exist What Service does Starbucks Provide Really what is their product.
- The pattern of numbers below is an arithmetic sequence tex 14 24 34 44 54 ldots tex Which statement describes the recursive function used to..
- Morgan felt the need to streamline Edison Electric What changes did Morgan make.
Rewritten by : Barada