We appreciate your visit to A one family dwelling has six 3 kW electric wall heaters with individual thermostats and five room air conditioners Two air conditioners are rated 10. This page offers clear insights and highlights the essential aspects of the topic. Our goal is to provide a helpful and engaging learning experience. Explore the content and find the answers you need!
Answer :
The volt amps that should be included (after demand factors) for the heating and air conditioning is 23.61678 kva.
How to solve for the volt ampere
If the heater coil is resistive the total KW thast is consumed by this bheter is given as
6 * 3 = 18KWA
We assume the connection that we have here to be in three phases. The two air conditioners are rated as
10.5 amp and 230 volts
√3 * 230 * 10.5
= 4.18278 KWA
KVA of three =
√3 *7.2 * 115
= 1.434
The total kva = 18 + 4.18278 + 1.434
= 23.61678 kva
Read more on volt ampere here:
https://brainly.com/question/9235824
#SPJ1
Thanks for taking the time to read A one family dwelling has six 3 kW electric wall heaters with individual thermostats and five room air conditioners Two air conditioners are rated 10. We hope the insights shared have been valuable and enhanced your understanding of the topic. Don�t hesitate to browse our website for more informative and engaging content!